The Enduraplas 75 Gallon Narrow Plastic Portable Diesel Fuel Boss Tank with Pump and Fuel Nozzle (MPN EP-RDU075N10D) is a polyethylene fuel storage tank designed for atmospheric non-pressurized service in farm, ranch, construction, and small-fleet fueling operations.
Design
- Polyethylene shell — corrosion-immune to diesel, biodiesel, waste-oil, and lubricant service
- NOT rated for gasoline, kerosene, jet-A, or other UEL/LEL-regulated fuels under most jurisdictions
- Atmospheric (non-pressurized) service only — vent must be installed per local fire-code requirements
- Above-ground service only unless explicitly UL-listed for underground fuel storage
- Top-centerline fill port; bottom or side outlet for gravity drain to pump or filtration assembly
Installation
Install on a level concrete pad with secondary containment sized for the full tank volume per EPA SPCC requirements where applicable (75-gallon tanks in commercial service typically trigger SPCC if total facility above-ground storage exceeds 1,320 gallons). Install a vent appropriate to the fuel service per NFPA 30, a low-permeability emergency vent for fire exposure, and a fuel-grade overfill-prevention valve at the fill port.
Common applications
- Construction-site diesel fueling for equipment and generator service
- Waste-oil collection at automotive, fleet-maintenance, and equipment-repair shops
- Generator day-tank reserve for backup power at commercial, healthcare, and data-center sites
- Small-fleet diesel and biodiesel staging for delivery and service operations
- Marine fuel storage at private and small-commercial docks (verify local code compliance)
- Aviation ground-equipment fuel transfer (non-aviation-fuel applications only — verify regulation)
Compatibility & compliance
Polyethylene shell is compatible with diesel, biodiesel (up to B100 in most cases — verify with OEM), waste oil, and lubricant service. NOT rated for gasoline, kerosene, jet-A, or other UEL/LEL-regulated fuels under most fire codes. Above-ground service only unless explicitly UL-listed for underground installation. Vent and overfill-prevention per NFPA 30 are required for most commercial installations.
Shipping
Ships LTL freight from the nearest manufacturing plant. ZIP-specific freight quotes are available through the freight estimator or by phoning 866-418-1777 with MPN EP-RDU075N10D.